Zadix Flow runs selected, versioned checks relevant to EU Regulation (EU) 2024/573. AI helps extract data; users review the record and applicable legal requirements.
EU Regulation 2024/573 entered into force on 11 March 2024, replacing Regulation 517/2014. It sets requirements for containment, recovery and records across EU member states.
Key obligations for HVAC operators and service companies:
Leak checks depend on gas category, charge and equipment type (Art. 5).
After repair, applicable equipment needs an effectiveness check after 24 operating hours and within one month; mobile equipment has an exception (Art. 4(5)).
Equipment subject to leak checks needs records of gas, work, personnel and results (Art. 7).
Certified technicians and companies required for all F-Gas work (Art. 5)
Applicable records must be available to authorities on request and retained for at least five years (Art. 7(2)).
Article 4(5)
Follow-up after leak repair
For equipment subject to leak checks, a certified person must verify a leak repair after at least 24 operating hours and within one month. Article 4(5) permits an immediate check for specified mobile equipment.
Article 5
Leak check intervals by CO₂e tier
Article 5 sets check intervals by Annex I CO₂-equivalent charge or Annex II Section 1 kilograms, with specific equipment exemptions and detection-system intervals.
Article 7
Record-keeping requirements
Article 7 specifies the equipment records required when leak checks apply, including gas movements, facility details where relevant, personnel, check results and repair results.
Architecture
AI extracts. Code decides.
AI — What it does
Reads equipment label photos with GPT-4o vision
Transcribes voice notes via Whisper
Extracts: equipment type, serial, refrigerant type, amounts, leak status
Assigns confidence scores to each extracted field
Generates 3-line review summary for technician confirmation
Falls back to structured template if extraction fails
Compliance engine — What it does
Runs configured checks against service events
Versioned checks relevant to EU 2024/573
Each rule traceable to a specific regulation article
Versioned per country (DE/NL/GB independently)
Produces compliance_flags[] with severity + suggested fix
AI never sees or overrides rule output — completely separate pipeline
The Rules
The checks shown in this guide
These checks are implemented in code and documented for review. They do not cover every legal obligation.
ERRORErrors — record cannot be finalized
FGAS-01Art. 7
Refrigerant type required
Triggered when any refrigerant is added or removed. Refrigerant type must be specified.
FGAS-02Art. 7
Recovery cylinder ID required
Triggered on disposal or decommission. Recovery cylinder ID must be recorded when refrigerant is removed.
FGAS-04Art. 7
Serial number required for disposal
Equipment serial number or unique identifier is mandatory when action type is disposal or decommission.
FGAS-05Art. 7(1)
Refrigerant source required
When refrigerant is added, its source must be declared: virgin, recycled, or reclaimed.
FGAS-06Art. 7(1)
Reclamation facility required
If source is reclaimed, the name of the reclamation facility must be recorded.
FGAS-07Art. 7(1)(g)
Recovered gas destination required
When refrigerant is removed, its destination must be declared: recycled, reclaimed, or destroyed.
FGAS-08Art. 5
Technician certificate required
F-Gas certificate number of the performing technician must be attached to every service record, no exceptions.
FGAS-09Art. 5
Company certificate required
Service company F-Gas certificate number must be attached to every service record.
WARNINGWarnings — record can finalize with office review
FGAS-03Art. 7
Recovery amount consistency
If refrigerant is removed, recovered amount must be recorded. Missing value may indicate unrecovered atmospheric release.
FGAS-11Art. 5
Leak check — 5–50 tCO₂e tier
Equipment in the 5–<50 tonne CO₂e tier requires leak checks every 12 months (24 with certified detection system).
FGAS-12Art. 5
Leak check — 50–500 tCO₂e tier
Equipment in the 50–<500 tonne CO₂e tier requires leak checks every 6 months (12 with certified detection system).
FGAS-13Art. 5
Leak check — ≥500 tCO₂e tier
Equipment at or above 500 tonne CO₂e requires leak checks every 3 months (6 with certified detection system).
INFOInformational — auto-action triggered
FGAS-10Art. 4(5)
Follow-up after leak repair
Where Article 4(5) applies, a certified person checks repair effectiveness after 24 operating hours and within one month, subject to the mobile-equipment exception.
Reference Data
GWP reference table (built-in)
CO₂-equivalent = system charge (kg) × GWP ÷ 1,000. Used to determine leak check tier automatically.
R32
GWP 675
R410A
GWP 2088
R134a
GWP 1430
R404A
GWP 3922
R407C
GWP 1774
R22
GWP 1810
R290
GWP 3
R744
GWP 1
R507A
GWP 3985
R448A
GWP 1387
R449A
GWP 1397
R452A
GWP 2141
R454B
GWP 466
R513A
GWP 631
R1234yf
GWP <1
Data & Privacy
Your data. Your control.
🇩🇪
Hosting and integrations
The service is self-hosted. Some integrations process data with third-party providers; see the privacy notice.
🔒
Multi-Tenant Isolation
Every record has company_id. CompanyScopeGuard enforces isolation. PostgreSQL Row Level Security as second layer.
📋
Privacy documentation
See our privacy notice and request the current processing and transfer details.
🔑
SHA-256 Tamper-Proof
Finalized records sealed with SHA-256 hash. Immutable PostgreSQL trigger prevents modification at database level.
📤
Data Portability
Full CSV and PDF export available at any time, including 90 days after cancellation.
🕵️
Audit Trail
An audit log helps trace views, overrides and status changes. Article 7 records must be retained for at least five years where applicable.
See the rules in action