Rules from the regulation.
Not from an AI.

Zadix Flow runs selected, versioned checks relevant to EU Regulation (EU) 2024/573. AI helps extract data; users review the record and applicable legal requirements.

UE 2024/573Regulación F-Gas UKConfigured checksPrivacy informationSelf-hosted

EU Regulation (EU) 2024/573

EU Regulation 2024/573 entered into force on 11 March 2024, replacing Regulation 517/2014. It sets requirements for containment, recovery and records across EU member states.

Key obligations for HVAC operators and service companies:

  • Leak checks depend on gas category, charge and equipment type (Art. 5).
  • After repair, applicable equipment needs an effectiveness check after 24 operating hours and within one month; mobile equipment has an exception (Art. 4(5)).
  • Equipment subject to leak checks needs records of gas, work, personnel and results (Art. 7).
  • Certified technicians and companies required for all F-Gas work (Art. 5)
  • Applicable records must be available to authorities on request and retained for at least five years (Art. 7(2)).
Article 4(5)

Follow-up after leak repair

For equipment subject to leak checks, a certified person must verify a leak repair after at least 24 operating hours and within one month. Article 4(5) permits an immediate check for specified mobile equipment.

Article 5

Leak check intervals by CO₂e tier

Article 5 sets check intervals by Annex I CO₂-equivalent charge or Annex II Section 1 kilograms, with specific equipment exemptions and detection-system intervals.

Article 7

Record-keeping requirements

Article 7 specifies the equipment records required when leak checks apply, including gas movements, facility details where relevant, personnel, check results and repair results.

AI extracts. Code decides.

AI — What it does

  • Reads equipment label photos with GPT-4o vision
  • Transcribes voice notes via Whisper
  • Extracts: equipment type, serial, refrigerant type, amounts, leak status
  • Assigns confidence scores to each extracted field
  • Generates 3-line review summary for technician confirmation
  • Falls back to structured template if extraction fails

Compliance engine — What it does

  • Runs configured checks against service events
  • Versioned checks relevant to EU 2024/573
  • Each rule traceable to a specific regulation article
  • Versioned per country (DE/NL/GB independently)
  • Produces compliance_flags[] with severity + suggested fix
  • Computes compliance_status: valid/risky/non_compliant
  • AI never sees or overrides rule output — completely separate pipeline

The checks shown in this guide

These checks are implemented in code and documented for review. They do not cover every legal obligation.

ERRORErrors — record cannot be finalized
FGAS-01Art. 7

Refrigerant type required

Triggered when any refrigerant is added or removed. Refrigerant type must be specified.

FGAS-02Art. 7

Recovery cylinder ID required

Triggered on disposal or decommission. Recovery cylinder ID must be recorded when refrigerant is removed.

FGAS-04Art. 7

Serial number required for disposal

Equipment serial number or unique identifier is mandatory when action type is disposal or decommission.

FGAS-05Art. 7(1)

Refrigerant source required

When refrigerant is added, its source must be declared: virgin, recycled, or reclaimed.

FGAS-06Art. 7(1)

Reclamation facility required

If source is reclaimed, the name of the reclamation facility must be recorded.

FGAS-07Art. 7(1)(g)

Recovered gas destination required

When refrigerant is removed, its destination must be declared: recycled, reclaimed, or destroyed.

FGAS-08Art. 5

Technician certificate required

F-Gas certificate number of the performing technician must be attached to every service record, no exceptions.

FGAS-09Art. 5

Company certificate required

Service company F-Gas certificate number must be attached to every service record.

WARNINGWarnings — record can finalize with office review
FGAS-03Art. 7

Recovery amount consistency

If refrigerant is removed, recovered amount must be recorded. Missing value may indicate unrecovered atmospheric release.

FGAS-11Art. 5

Leak check — 5–50 tCO₂e tier

Equipment in the 5–<50 tonne CO₂e tier requires leak checks every 12 months (24 with certified detection system).

FGAS-12Art. 5

Leak check — 50–500 tCO₂e tier

Equipment in the 50–<500 tonne CO₂e tier requires leak checks every 6 months (12 with certified detection system).

FGAS-13Art. 5

Leak check — ≥500 tCO₂e tier

Equipment at or above 500 tonne CO₂e requires leak checks every 3 months (6 with certified detection system).

INFOInformational — auto-action triggered
FGAS-10Art. 4(5)

Follow-up after leak repair

Where Article 4(5) applies, a certified person checks repair effectiveness after 24 operating hours and within one month, subject to the mobile-equipment exception.

GWP reference table (built-in)

CO₂-equivalent = system charge (kg) × GWP ÷ 1,000. Used to determine leak check tier automatically.

R32

GWP 675

R410A

GWP 2088

R134a

GWP 1430

R404A

GWP 3922

R407C

GWP 1774

R22

GWP 1810

R290

GWP 3

R744

GWP 1

R507A

GWP 3985

R448A

GWP 1387

R449A

GWP 1397

R452A

GWP 2141

R454B

GWP 466

R513A

GWP 631

R1234yf

GWP <1

Your data. Your control.

🇩🇪

Hosting and integrations

The service is self-hosted. Some integrations process data with third-party providers; see the privacy notice.

🔒

Multi-Tenant Isolation

Every record has company_id. CompanyScopeGuard enforces isolation. PostgreSQL Row Level Security as second layer.

📋

Privacy documentation

See our privacy notice and request the current processing and transfer details.

🔑

SHA-256 Tamper-Proof

Finalized records sealed with SHA-256 hash. Immutable PostgreSQL trigger prevents modification at database level.

📤

Data Portability

Full CSV and PDF export available at any time, including 90 days after cancellation.

🕵️

Audit Trail

An audit log helps trace views, overrides and status changes. Article 7 records must be retained for at least five years where applicable.

See the rules in action